Technical DataACRD100 ACRD101 ACRD200 ACRD201ACRD500ACRD501ACRD502InRow® RDAir-Cooled/Fluid-Cooled - 50/60 HzDATA CENTER SOLUTIONSFor More Information
InRow RD Technical Data Manual4Standard FeaturesCabinetThe frame is constructed of 16 gauge formed steel for maximum strength. The cabinet is servicea
5InRow RD Technical Data ManualOptional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possi-ble lea
InRow RD Technical Data Manual6Microprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each unit. The controll
7InRow RD Technical Data ManualAlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:All series:
InRow RD Technical Data Manual8InRow RD ModelsExterior components: ACRD100 and ACRD200 seriesRemovable rear doorAdjustable leveling feetSide panel
9InRow RD Technical Data ManualInterior components (front): ACRD100 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2
InRow RD Technical Data Manual10Interior components (rear): ACRD100 seriesFilter/dryerHot gas bypass valvePressure transducer (2 total, located beh
11InRow RD Technical Data ManualInterior components (front): ACRD200 seriesElectrical control box 1 (retractable)CompressorElectrical control box 2
InRow RD Technical Data Manual12Interior components (rear): ACRD200 seriesFilter/dryerElectrical control box 2Pressure transducer (2 total, located
13InRow RD Technical Data ManualExterior components: ACRD500 seriesRemovable rear doorsCasters (all swiveling)Side panel lockDoor handle and lock
American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be
InRow RD Technical Data Manual14Interior components (front): ACRD500 seriesCondensate drain panFan (2)Thermal expansion valveFan guard (2)Compres
15InRow RD Technical Data ManualInterior components (rear): ACRD500 seriesTable 1: Evaporator coilShutoff valvesCondensate drain panAir filtersSi
InRow RD Technical Data Manual16Electrical panel: ACRD100 and ACRD200 seriesLeak detector portBuilding management system (BMS) RS-485 portRemote te
17InRow RD Technical Data ManualElectrical panel: ACRD500 seriesTransformersUser interface connectorsMain controller boardRelay boardGround lugM
InRow RD Technical Data Manual18User interface panel: ACRD500 seriesRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNetwork portConsole
19InRow RD Technical Data ManualPerformance SpecificationsNet Cooling Capacity (Air and Glycol Cooled)Return Air Temperature SKU Total Capacity kW (BT
InRow RD Technical Data Manual20Net Cooling Capacity (Water Cooled)Return Air Temperature SKU Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)
21InRow RD Technical Data ManualPerformance at Percentage of Fan SpeedACRD100 Series% Fan SpeedVoltage/Phase/HzL/S (SCFM)Unit Power in kWCondenser Fan
InRow RD Technical Data Manual22ACRD200 Series% Fan SpeedVoltage/Phase/Hz L/S (SCFM) Unit Power in kWNet Sensible Capacity kW (BTU/h) SA Temp °C (°F)R
23InRow RD Technical Data ManualACRD500 Series% Fan Speed Voltage L/S (SCFM) Unit Power in kWCondenser Fan Power in kWNet Sensible Capacity kW (BTU/h)
ContentsInRow RD Technical Data ManualiOverview ... 1Scalable Solution for Crit
InRow RD Technical Data Manual24General DataGeneral Specifications - ACRD200 SeriesData Units Water Cooled Glycol Mixture CooledNominal flow rate ente
25InRow RD Technical Data ManualAir CooledData SKU ValueAIR SYSTEM - FAN (Standard Filter Installed)Size - mm (in)ACRD100 200 (7.9)ACRD101 200 (7.9)AC
InRow RD Technical Data Manual26 Electrical DataAltitude Correction FactorsRoom Condition: 72 DB/50% RHAltitude (ft) 0 1000 2000 3000 4000 5000 6000 7
27InRow RD Technical Data ManualDimensional DataACRD100 and ACRD200 seriesDimensions are shown in mm (in).na2231b
InRow RD Technical Data Manual28ACRD500 seriesDimensions are shown in mm (in).na2465a
29InRow RD Technical Data ManualNetShelter SX to VX Height Adapter: ACRD100 and ACRD200 seriesNetShelter SX to VX Height Adapter: ACRD500 seriesNetShe
InRow RD Technical Data Manual30Piping and Mechanical ConnectionsRefrigeration Piping Diagram (ACRD100 and ACRD500 series)Note: Shutoff valves shown n
31InRow RD Technical Data ManualWater cooled piping (ACRD200 series)Note: Bottom piping shown.InRow RDGate valveBalancing valveHose bib*Strainer,
InRow RD Technical Data Manual32Glycol cooled piping (ACRD200 series)Note: Bottom piping shown.Expansion tank*Hose bibs*Tank fill*Gate valves*Flu
33InRow RD Technical Data ManualTop piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Low voltage
InRow RD Technical Data ManualiiPerformance Specifications ... 19Net Cooling Capacity (Air and Glycol Cooled) .
InRow RD Technical Data Manual34Bottom piping and power access locations (ACRD100 series and ACRD200 series)Dimensions are shown in mm (in).Electrica
35InRow RD Technical Data ManualTop piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant discharge lineRefr
InRow RD Technical Data Manual36Bottom piping and power access locations (ACRD500 series)Dimensions are shown in mm (in).Refrigerant liquid lineRefr
37InRow RD Technical Data ManualOutdoor Heat ExchangersAir Cooled Condensers - Mechanical Data (ACRD100 Series)Air Cooled Condensers Mechanical Data (
InRow RD Technical Data Manual38Air Cooled Condensers - Electrical Data (ACRD100 Series)SKU Voltage Phase Frequency FLA MCA MOPACCD75214 208-240V 1 ph
39InRow RD Technical Data ManualACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in). Conden
InRow RD Technical Data Manual40ACCD75207ACCD75208 and ACCD75209Condensers shown above have 16 mm (0.63 in) mounting holes on each of their lower legs
41InRow RD Technical Data ManualACCD75216, ACCD75218, and ACCD75220ACCD75217 and ACCD75219ACFC75210ACFC75255Dimensions are shown in mm (in).na2893ana2
InRow RD Technical Data Manual42ACFC75256ACFC75257Dimensions are shown in mm (in).Air-cooled Condenser FeaturesAvailable in one to three fan configura
43InRow RD Technical Data ManualGuide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for
InRow RD Technical Data ManualiiiGuide Specifications ...43Guidelines for Installation . . . . . .
InRow RD Technical Data Manual443. All exterior panels and frame shall be powder coated for durability and attractive finish. Exterior frame and panel
45InRow RD Technical Data Manual3. Alarms: The microprocessor controller shall activate a visible and audible alarm in the occurrence of the following
InRow RD Technical Data Manual46F. Cooling Coil And Condensate Pan1. ACRD100 and ACRD200 series:a. The cooling coil shall use corrugated aluminum fin
47InRow RD Technical Data ManualJ. Temperature Sensors1. Internal Temperature Sensors: Thermistor temperature sensors shall be mounted behind the fron
InRow RD Technical Data Manual48Guidelines for InstallationThe InRow RD provides reliable, accurate temperature control of computer rooms, laboratorie
6/2010990-3236D-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following
1InRow RD Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a
InRow RD Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin
3InRow RD Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d