Section 6: SPDU Guide Specifications
62 SPDU Technical Handbook
l. K Factor
m. Crest Factor
n. Discrete Input and Output Status
o. Analog Input Reading
p. Custom: User programmable display of any combination of
up to seven metered values
2. All three phases of three-phase parameters must be displayed simultaneously. All voltage
and current parameters must be monitored using true RMS measurements.
E. Premium-level Alarm Annunciation
1. The Premium-level monitoring system must also supervise and annunciate the following:
a. Output Over Voltage: Line-to-line for all three phases
b. Output Over Voltage: Line-to-neutral for all three phases
c. Output Under Voltage: Line-to-line for all three phases
d. Output Under Voltage: Line-to-neutral for all three phases
e. Maximum Thresholds:
1.) Current: All three phases, neutral and ground
2.) Voltage: Neutral to ground
3.) System Power: Watts, kVA
4.) Frequency
5.) % THD
f. Minimum Thresholds:
1.) Current: All three phases
2.) System Power: Watts, kVA
3.) Frequency
g. Voltage Phase Unbalance: Line-to-line for all three phases
h. Voltage Phase Unbalance: Line-to-neutral for all three phases
i. Current Phase Unbalance: All three phases
j. Discrete Input Energized: All discrete inputs
k. Reverse Sequence Error
2. All Alarms must be stored in non-volatile memory until manually reset.
F. Premium-level Custom Alarm Annunciation
1. The Premium-level monitoring system must also be capable of providing up to four (4)
Form C (NO/NC) relay contact enclosure outputs.
2. These relays must be independently programmable to actuate one event condition and/or a
combination of metered event conditions.