16 APC Redundant Switch: Installation and Operation Manual
Operation
Emergency
Power Off
You can use a remotely operated Emergency Power Off (
EPO
)
switch to turn off the
UPS
and disconnect power to the
equipment load. When you turn off the
UPS
through the
Emergency Power Off system, it will turn off immediately
without switching to battery operation.
1. Use the
EPO
connector.
2. Use a normally-open contact to connect the +24 terminal
to the
IN
terminal.
3. Wire the external blue four-pin female connector to the
emergency power off system.
Electrical
Hazard
Use only a licensed electrician to perform the
following procedure to connect the Redundant
Switch and its attached UPSs to your
Emergency Power Off system.
Caution
The
EPO
interface is a Safety Extra Low Voltage
(
SELV
) circuit. Connect it only to other
SELV
circuits.
The
EPO
interface monitors circuits that have no
determined voltage potential. Such closure
circuits may be provided by a switch or relay
properly isolated from the utility. To avoid
damage to the Redundant Switch, do not connect
the
EPO
interface to any circuit other than a
closure type circuit.