InRow RC Operation and Maintenance24
Return Air High Temperature
Violation
Warning • Make sure the Return Air threshold is set correctly in the Set Unit
Threshlds screen.
• If the problem persists, contact APC Customer Support.
Return Air Sensor Fault Critical • Make sure the sensor is connected properly.
• Replace the sensor.
• If the problem persists, contact APC Customer Support.
Supply Air High
Temperature Violation
Warning • Make sure the temperature sensor is connected properly.
• Make sure the Supply Air threshold is set correctly in the Set Unit
Threshlds screen.
• If the problem persists, contact APC Customer Support.
Supply Air Sensor Fault
(upper or lower)
Critical • Make sure the faulty sensor is connected properly.
• Replace the sensor.
• If the problem persists, contact APC Customer Support.
Supply Humidity Sensor
Fault
Critical • Make sure the sensor is connected properly.
• Replace the sensor.
• If the problem persists, contact APC Customer Support.
Water Detection Fault Warning • Identify and isolate the source of the leak.
• For assistance, contact APC Customer Support.