8
NetBotz Wireless Temperature Sensor Installation Guide
LED activity
The LED on the sensor blinks to indicate certain statuses or alerts.
During the boot process, LED activity on the Wireless Temperature Sensor is as
follows:
Note: If the LED flashes red three times, then slowly flashes red,
contact Technical Support.
The following table lists possible LED activity and its meaning:
To conserve power, the sensor will attempt to join the network after waiting the
following number of seconds: 5, 15, 30, 60, 120, 300, 300, 600, 600, 1200.
If the attempts to rejoin the network fail, the sensor will scan the network every
six hours to re-try the connection. If it cannot join the network after
approximately 24 hours, it will reboot, and attempt to join the network again,
repeating the wait interval starting at 5 seconds, until it joins the network.
To force an attempt to join the network, press the reset button.
LED Activity Meaning
Flashes a quick green, yellow, red
sequence
Power on
Alternately flashes green and yellow for
about 45 seconds
Runtime check
Flashes green three times Check OK
Turns solid yellow for 5 seconds Firmware update check
Flashes a quick green, yellow, green
sequence
Ready to attempt to join the network
LED Activity Meaning
Flashes yellow twice every 2 seconds Searching for network
Turns solid green, then turns off Joined the network
Off • Joined the network
• Has not joined the network, and is
conserving battery power.
Commentaires sur ces manuels