10 Environmental Monitoring Card
Specifications
Product
specifications
Item Specification
Electrical
Operating voltage 16 27 VDC
Operating current
draw
30 mA DC (exclusive of any attached
sensors)
Temperature accuracy
± 2° C (±3.6° F) from 0 to 40° C
(32 to 104° F)
Humidity accuracy
± 8% RH, 10 to 90% RH
at 25° C (77° F)
± 8% RH, 30 to 80 % RH
from 15 to 30° C (from 59 to 95° F)
Physical
Size (h × w × d)
3.8 cm × 10.2 × 10.2
(1.5 i × n4 × 4)
Weight 140 g (0.3 lb)
Shipping weight 320 g (0.7 lb)
Environmental
Elevation:
Operating:
Storage:
0 to 3000 m (0 to 10,000 ft)
0 to 15 000 m (0 to 50,000 ft)
Temperature:
Operating:
Storage:
0 to 40° C (32 to 104° F)
25 to 65° C (–13 to 149° F)
Probe operating
temperature
0 to 60° C (32 to 140° F)
Approvals
EMC verification
FCC Class A, DOC Class A, EN55022
Class A
Electromagnetic
immunity
EN55024 verified