Electrical Data
APC InRow SC Technical Data Manual 11
Electrical Data
Note: *Rated Current is the maximum current draw for the input voltage range
**Rated Power is maximum power consumption expected during normal operations, actual power draw may vary based upon operating conditions
***In-Rush is of short duration and only occurs during start-up and compressor cycling.
SKU
Rated In-Rush***
Plug
Type
Vo l t a ge
(Volts)
Phase
Frequency
(Hz)
Current*
(Amps)
Power**
(Watts)
Power
Factor
Duration
(ms)
Peak
Current
(Amps)
Power
(Watts)
ACSC100 208-230 1 60 16.0 2940 0.98 200 56.0 8240
ACSC101 220-240 1 50 14.4 2390 0.98 60 65.0 10100