Operation
WARNING:Forsafetyreasons,onlyqualiedpersonnelisallowedtoperformthe
operationproceduresdescribedinthischapter.
Modes
TheUPShasdifferentoperationmodes.IftheinstallationincludesaMaintenanceBypassPanel(MBP),
anexternalmaintenancebypassoperationmodewillalsobeavailable.
NormalOperation
TheUPSconvertsutility/mainspowertoconditionedpowerfortheconnectedload.
BatteryOperation
TheUPSprovidespowertotheconnectedloadfromitsinternaland(ifavailable)externalbatteriesfor
aniteperiod.TheUPStransferstobatteryoperationifthesupplyofutility/mainspowerfails,oris
outsidethepre-denedlimits.
InternalBypassOperation
Internalbypasskeepstheloadsuppliedwithutility/mainspowerduringmaintenanceoftheUPSpower
sections.Ininternalbypassoperation,utility/mainspowerissentdirectlytotheconnectedloadbypassing
allinternalUPSfunctionsandlters.Batteryback-upisnotavailableininternalbypassoperationeven
thoughthebatteriesareinplace.
ExternalMaintenanceBypassOperation
TheUPScanbeconnectedtoanoptionalexternalMBP .Whenactivated,thispanelbypassestheentire
UPSenclosure,feedingutility/mainspowerdirectlytotheload.AnactivatedexternalMBPcompletely
isolatestheUPSandallowsmaintenancetobeperformed.AnexternalMBPismandatoryiftheUPS
isrunninginparallel.
OptionalParallelOperation
TheconnectedloadispoweredbymultipleUPSunitstoincreasesystemredundancyortoincreasepower.
Theinternalmechanicalbypassleverisnotavailable.