Technical Data InfraStruXure™ InRow SC Air-Cooled Self-Contained- 50/60Hz
APC InRow SC Technical Data Manual 7na2229aComponentsExternal ViewIntake Air DuctAdjustable Leveling Foot (4 places)Removable Rear DoorDisplay Int
Components8 APC InRow SC Technical Data ManualInternal ViewCondenser CoilRefrigeration Filter DrierCondenser FansHot Gas Bypass ValveCompressorP
9 APC InRow SC Technical Data ManualAir-cooled Performance SpecificationsNote: Room condition 72oF db/50% RH. Density ratio is used for air flow corre
APC InRow SC Technical Data Manual 10General Technical SpecificationsMODEL ACSC100 ACSC101ELECTRICAL INPUT 200-240V, 1ph, 60Hz 200-240V, 1ph, 50HzAIR
Electrical DataAPC InRow SC Technical Data Manual 11Electrical DataNote: *Rated Current is the maximum current draw for the input voltage range**Rated
Sound Performance Data12 APC InRow SC Technical Data ManualSound Performance DataAir-Cooled Tested Sound DataFan Speed%Evaporator Air-flow Rate (SCFM)
APC InRow SC Technical Data Manual 13Dimensional DataInRow SC Assembled ModuleDimensions are inches (millimeters)n a2 231 a
Mechanical Connections14 APC InRow SC Technical Data ManualMechanical ConnectionsInRow SC Condensate Line and Power ConnectionsDimensions are inches (
APC InRow SC Technical Data Manual 15Guidelines for InstallationThe InRow SC provides reliable, self-contained cooling that maximizes availability wit
Guidelines for Installation16 APC InRow SC Technical Data ManualService AccessRoutine service and basic repair activities can be accomplished with fro
ContentsiOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1InRow SC System Overview . . . . .
APC InRow SC Technical Data Manual 17Guide SpecificationsStandard ComponentsA. CABINET CONSTRUCTION1. Exterior panels shall be 18 gauge metal with 5 l
Guide Specifications18 APC InRow SC Technical Data ManualD. MICROPROCESSOR CONTROLLER1. Monitoring and Configuration: The master display shall allow m
Guide SpecificationsAPC InRow SC Technical Data Manual 194. Logging: The microprocessor controller shall log and display all available events. Each al
Guide Specifications20 APC InRow SC Technical Data ManualCeiling tile adapter shall be suitable for either 24in x 24in or 600mm x 600mm suspended ceil
APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following ways:• Visit the AP
APC InRow SC Technical Data Manual 1OverviewThe InRow SC offers efficient, effective and economical cooling for a variety of wiring closets and server
InRow SC System Overview2 APC InRow SC Technical Data ManualInRow SC System OverviewSelf Contained SystemAn air-cooled self-contained system has all t
Application Guidelines3 APC InRow SC Technical Data ManualApplication GuidelinesSelf-Contained SystemThe InfraStruXure InRow SC self-contained unit is
4 APC InRow SC Technical Data ManualStandard FeaturesVariable Speed Direct Drive Tubeaxial FansEach unit is equipped with six 200mm mixed flow, direct
5 APC InRow SC Technical Data ManualOptional FeaturesRope Water DetectorsThe solid-state spot water detector activates an audible alarm on the control
Microprocessor ControllerAPC InRow SC Technical Data Manual 6Microprocessor ControllerMicroprocessor Controller The microprocessor controller is stand