MasterSwitch Power Distribution Unit User’s Guide 48
Product Information
Specifications continued
Product
specifications for
AP9217
Continued on next page
Type of
Specification
Item Specification
Electrical Input:
Nominal input voltage
Acceptable input voltage
Nominal input frequency
Overcurrent protection
Input connector
100–120 VAC
90140 VAC
50/60
Hz
20-A
circuit breaker
12
ft (3.7 m) attached,
NEMA
L5-20, twist lock cord
Output:
Output connectors Eight
NEMA 5-15
outlets
Maximum total current draw:
16A
Physical Size (
H × W × D
)
1.75 × 17.0 × 6.5
in
(
4.4× 43.2 × 16.5
cm)
Weight: 6.6 lb (3.0
kg)
Shipping weight:
9.0
lb (
4.1
kg)
Environmental Elevation (above MSL
):
Operating
Storage
0
to
10,000
ft (
0
to
3000
m)
0
to
50,000
ft (
0
to
15 000
m)
Temperature:
Operating
Storage
32
to
104°F
(
0
to
40°C
)
32
to
113°F
(
0
to
45°C
)
Operating Humidity: 0
to
95%
, non-condensing
Approvals EMC
verification:
FCC
Class
A
;
DOC
Class A;
VCCI
Safety Agency: