InRoom CW/DX – Operating Instructions 11
Air fl ow (D)
A distinction is made between downfl ow and upfl ow cooling units in respect of air fl ow. On downfl ow units the
room air is drawn in to the cooling units from above and passed down into the raised fl oor void. On upfl ow
units the room air is drawn in from the front side of the cooling unit and passed upward.
Upfl ow
supply air
room / return air
room / return air
supply air
Downfl ow
Number of refrigerant circuits
The cooling units exist with either one or two refrigerant circuits. This concerns the cooling systems A, ACW,
G, GCW and GE.
The two-circuit units are equipped with two individual refrigerant circuits which are identical.
The two-circuit G-, GCW- and GE-units only have one water circuit which contains - except two condensers
- the same number of components as the single circuit version.
All ACW-, GCW- and GE-units contain only one free cooling CW/GE-coil.
The maximally available pressure at the airside is reduced by double heat exchanger coils.