APC PTEL1-4 Fiche technique Page 4

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 8
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 3
English
User Manual for PTEL1-4
1. Introduction
Thank you for purchasing this American Power Conversion 4-
line telephone surge protector, model PTEL1-4. It protects tele-
phones, voice mail and automated answering systems, fax ma-
chines and modems from damage caused by lightning-generated
electrical transients. Each PTEL1-4 protects up to 4 lines. PTEL1-4
includes grounding cables and wall mount/stacking brackets. See
figure 1. Use as many PTEL1-4s as needed to protect your systems.
Up to 10 PTEL1-4s can be rack mounted using the APC rack mount-
ing kit, part number PRM, available from your dealer or from
APC at 1-800-800-4APC (or 1-401-789-5735). See Figure 2 for
optional rack mount configuration.
Please fill out and return the enclosed warranty registration card.
2. Safety
Please read and save these instructions, and take the following
safety precautions.
n Use the PTEL1-4 in a protected environment only.
n Never install telephone wiring during a lightning storm.
n Follow the installation instructions carefully. The current-
limiting feature in this product could be rendered inoperable
if the product is improperly installed.
n To fully protect the user and equipment, the product must be
connected to a proper ground, as described in section 3.
3. Installation
Setting up the ProtectNet
1. Refer to figure 3. Using telephone cords, connect the PTEL1-4
IN jacks to the nearest phone wall outlets .
2. Connect the devices to be protected (e.g. modem or fax ma-
chine) to the PTEL1-4 OUT jacks .
3. Connect the PTEL1-4 ground wire terminal to a proper ground
(protective earth) as described in the section on grounding
below.
4. The PTEL1-4 can be placed on a flat surface, mounted on a wall,
stacked, or mounted on the optional rack shelf. See figure 4 for a
typical rack mount installation. See figure 5 for a typical surface
installation.
Grounding the ProtectNet
1. Verify that the protected equipment is plugged into a three-wire
grounded outlet, if applicable. If your site has outlets with only
two holes (no center ground), a qualified electrician should be
called to upgrade your building wiring. Many APC UPS and surge
suppression products have a Site Wiring Fault Indicator that warns
of improper building wiring, including lack of a safety ground. An
outlet wiring tester can be purchased at most hardware stores,
though it is not as sensitive. Use of APC power protection equip-
ment is recommended.
2. For ganged, stacked, or rack mounted units connect the sup-
plied short grounding wire from PTEL1-4 to PTEL1-4 daisy chain
fashion. Then use the supplied long ground wire to make the ground
connection. Ground the PTEL1-4 by choosing one of the follow-
ing measures, listed in order of preference. Do not ground to the
rack mount shelf.
n Many APC UPSs provide a TVSS Ground screw for fasten-
ing the ground terminal. Use this screw wherever possible.
Again, verify that the UPS is plugged into a three-wire
grounded outlet.
Page 2
n Fasten the ground wire to the phone system ground, if pos-
sible, or beneath the head of a metal screw on the chassis of
the protected equipment. Do not loosen chassis screws that
secure internal components.
n Fasten the ground terminal beneath the head of a wall outlet
cover plate (120V systems only). Where possible, this should
be the same outlet where your protected equipment is plugged
in.
CAUTION: Disconnect power to the outlet by removing the branch
fuse or switching off the circuit breaker before attempting to
loosen the cover plate screw. Do not overtighten the screw.
n Fasten the ground terminal beneath a clamp secured around
a cold water pipe.
4. Specifications
Lines protected: 4 and 5 on RJ-45 connector, accepts RJ-45 & RJ-
11 plugs.
Mode of protection: metallic (Tip - Ring) and longitudinal (Tip +
Ring - Ground).
Peak voltage: ± 6,000 Volts, 1.2/50 µs test waveform.
Peak current: 150 Amps, 8/20 µs test waveform.
Breakover: (turn on) voltage: 260V peak nominal between tip and
ring.
Overload protection: solid state self-resetting fuse.
Response time: < 5 ns.
Agency approvals: Listed UL 497A, CSA certified per CSA C22.2
No. 226.
Vue de la page 3
1 2 3 4 5 6 7 8

Commentaires sur ces manuels

Pas de commentaire