APC ACRC500 Manuel d'installation Page 23

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 48
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 22
15InRow RC Operation and Maintenance
Setpoints
Path: Main > Set Group Setpoints
A setpoint is the target value that a cooling group tries to maintain in the rack. The default setpoints are
appropriate for most cooling applications.
The setpoints for each mode must be within the following ranges:
Cool: 18.025.0°C (64.477.0°F)
Supply Air: 17.023.0°C (62.6–73.4°F)
Note: The Supply Air setting is defined when the cooling group is commissioned. This
task is performed by APC authorized personnel only.
Note: If the Supply Air setpoint is greater than the Cool setpoint, the cooling unit
triggers an alarm and resets the Supply Air setpoint to equal the Cool setpoint.
Fan Spd: Set the fan speed preference that will give you the desired temperature difference (DT).
Each fan speed provides an approximate DT between the supply air from the equipment and the
air returned from the rack.
Low = 16.7°C (30°F) DT
Med-Low = 13.9°C (25°F) DT
Med = 11.1°C (20°F) DT
Med-High = 6.3°C (15°F) DT
High = 5.6°C (10°F) DT
Note: The cooling group will automatically override this fan speed setting and adjust
the fan speed to provide optimum cooling for the environment as needed.
PID settings
Path: Main > Set Group PIDs
The Proportional plus Integral plus Derivative (PID) loop controls the output of the fans.
Caution: This procedure is to be performed by APC authorized personnel only. Improperly
set PID controls could result in equipment damage.
Gain (P). The proportional multiplier (gain) for this mode or actuator. The proportional multiplier
adjusts for the difference (error) between the measured value and the setpoint.
Rate (I). The integral multiplier (reset rate) for this mode or actuator. The integral multiplier adjusts for
error measurement and the amount of time that the error has existed. The integral multiplier adds to or
subtracts from the output in small increments to correct for the offset error caused by the proportional
contribution.
Deriv (D). The derivative multiplier (derivative) for this mode or actuator. The derivative multiplier
adjusts the output for rapid changes in the error, correcting for the rate of change of the error over time.
Vue de la page 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 47 48

Commentaires sur ces manuels

Pas de commentaire