37InRow RC Operation and Maintenance
Troubleshooting
Problem Possible Cause Corrective Action
Controls erratic or
inoperative
• Inlet temperature to cooling
unit is higher than rated
maximum temperature
• Reduce the load or add additional cooling equipment.
Fans fail to start • Cooling unit shutdown due to
an external command
• Temporarily remove the input contact cable, if it is
connected.
• Single fan fails to start • Verify that the farn circuit breaker is ON.
Cooling unit cannot
obtain setpoint
Improper placement of remote
temperature sensor
Verify that the remote temperature sensor is properly located
in the cold aisle.
• Dirty filter • Clean the filter.
• Dirty coil • Clean the coil.
• Valve/actuator malfunction • Fully open the valve.
• Application error • Contact APC at a number located on the rear of this manual.
• Entering water temperature is
too high
• Verify that the temperature of the Cooling Unit water supply
is within the specified range.
• Heat load is too far away • Place the cooling unit closer to the heat load.
Water carryover • Improper fan speed selected • RACS and HACS modes only: Select the next-highest fan
speed setting. For example, change the fan speed setting
from Low to Med/Low.
• Inlet water temperature is too
low
• Verify that the temperature of the inlet water is within the
specified range.
• Room humidity is too
high/low
• Improve room sealing.
Temperature control
not tight enough
Improper placement of remote
temperature sensor
Verify that the remote temperature sensor is properly located
in the cold aisle.
Water on outside of
cooling unit
• Condensate drain hose is not
connected or not properly
routed outside the cooling unit
• Verify that the condensate drain hose is properly connected
to the pump and properly routed outside of the cooling unit.
• Verify that the condensate drain line does not exceed 5.4 m
(18 ft) lift and 18.3 m (60.0 ft) horizontal run.
• Leak in drain system • Locate and repair the leak.
• Cooling unit not leveled
properly
• Adjust the leveling feet of the cooling unit.
• Damaged piping insulation • Identify damaged area and repair the insulation.
Fluid valve not
responsive
• Actuator not connected
properly
• Verify that the actuator is connected properly.
• Actuator and shaft not
rotating together
• Tighten the linkage screw on the actuator shaft.
• Rotary switch on the bottom
of the actuator is set
incorrectly
Confirm that the rotary switch is pointing toward the front of
the cooling unit.
Display interface not
operational, but
cooling unit operates
• Display interface not
connected properly
• Verify that the display interface cable is connected properly.