USER’S GUIDE
AUTOMATIC TRANSFER SWITCH
160
The Upload Event and its Error Messages
The event and its error messages
The following system event occurs when the receiving Automatic Transfer
Switch completes using the .ini file to update its settings.
Configuration file upload complete, with number valid values
This event has no default severity level.
If a keyword, section name, or value is invalid, the event text is extended to
include notification of the following errors.
The export to and the subsequent upload by the receiving
Automatic Transfer Switch succeeds even if there are errors.
Event text Description
Configuration file warning: Invalid
keyword on line number.
Configuration file warning: Invalid
value on line number.
A line with an invalid keyword or value is ignored.
Configuration file warning: Invalid
section on line number.
If a section name is invalid, all keyword/value pairs
in that section are ignored.
Configuration file warning:
Keyword found outside of a
section on line number.
A keyword entered at the beginning of the file (i.e.,
before any section headings) is ignored.
Configuration file warning:
Configuration file exceeds
maximum size.
If the file is too large, the Automatic Transfer Switch
stores and processes what it can, but ignores what it
cannot. Reduce the size of the file, or divide it into
two files, and try uploading again.