InRoom Controller - Operating Instructions60
K6
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Cooling
Drycooler
In the first line you add the drycooler to the
configuration by entering "1". With "0" you
disable the drycooler.
With the parameter "D-OUT" you determi-
ne a digital output for the drycooler on/off
signal.
The digital input for the drycooler alarm can
be assigned by the "D-IN" parameter.
The drycooler runtime can be set in the
last line.
Note:
For the dry cooler control, the configuration
of an outside temperature sensor and a
water temperature sensor is required.
drycool 1 conf 1
drycool 1 dout 10
drycool 1 alarm 5
drycool 1 runtime 150