APC INROOM ACPSC3000 Instructions d'exploitation Page 62

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 106
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 61
InRoom Controller - Operating Instructions62
N1
N2
N3
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Heating
E-heating/Hotgas reheat/Hot
water reheat
Setting the parameter ACTIVE to 1 adds
a reheat to the configuration. Setting this
parameter to 0 disables the reheat.
In the next line you determine the reheat
type (1: reheat with on/off control, 2: reheat
with proportional control).
With the parameter "D-OUT" you determine
a digital output for the reheat. As the propor
-
tional electric reheat is controlled by pulse
width modulation, the reheat receives the
control signal by the digital output.
The digital input for the electric reheat alarm
can be assigned by the "D-IN" parameter.
The electric reheat runtime can be set in
the last line.
With the parameter "A-OUT" you adjust the
analogous output of the proportional signal
for the pww-valve of a pww-reheat.
eheat 1 conf 1
eheat 1 type 1
eheat 1 dout 3
eheat 1 alarm 7
eheat 1 runtime 0
pwwheat 1 conf 2
pwwheat 1 type 1
pwwheat 1 dout 5
pwwheat 1 aout 8
gasheat 1 conf 1
gasheat 1 dout 10
Vue de la page 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 105 106

Commentaires sur ces manuels

Pas de commentaire