73InRoom Controller - Operating Instructions
➊
➋
➌
➍
➎
Q3
Q4
Service
The corresponding commands:
Display Gen. settings
UPS
You can define the air conditioning func-
tions for operation with an Uninterrupted
Power Supply.
If the controller receives the signal at its
digital input for UPS operation, all the
functions which are enabled by "1" will be
admitted, whereas the functions with a "0"
will be disabled.
Note that also the fan speed will be re
-
duced to a pre-adjusted value in case of
UPS-operation. See page 51.
Interfaces
The global address can be adjusted in a
range from 1 to 255.
This address is decisive for the communi
-
cation with a BMS.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
ups cool 1
ups heat 0
ups humi 0
ups dehumi 0
globadr 231
Commentaires sur ces manuels