APC PDPB150G6F Guide de l'utilisateur Page 48

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 116
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 47
User Guide InfraStruxure 150kVA Power Distribution Unit 40
subfdThrLo
Access: Administrator, Device
Description: Configure the low load alarm threshold and warning alarm for the target subfeed.
Parameters: [[<thresh>] [ <enable|disable>]]
Thresh = % rated load
Example:
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,20%,Disable,10%,Disable
apc> subfdThrLo 25 enable
1. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,10%,Disable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,10%,Disable
subfdThrMn
Access: Administrator, Device
Description: Configure the minimum load alarm threshold and critical alarm for target subfeed.
Parameters: [[<thresh>] [ <enable|disable>]]
Thresh = % rated load
Example:
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,10%,Disable
apc> subfdThrMn 5 enable
1. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
Vue de la page 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 115 116

Commentaires sur ces manuels

Pas de commentaire