APC PDPB150G6F Guide de l'utilisateur Page 49

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 116
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 48
41User Guide InfraStruxure 150kVA Power Distribution Unit
subfdBrkr
Access: Administrator, Device
Description: Configure the breaker position critical alarm for the target subfeed.
Parameters: [<enable|disable>]
Example:
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
apc> subfdBrkr disable
1. Disable,Disable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Disable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
subfdRstkWh
Access: Administrator, Device
Description: Reset the energy usage and usage date for the target subfeed.
subfdTarget 1 = Panel board 1
subfdTarget 2 = Panel board 2
subfdTarget 3 = Subfeed
Example:
apc> subfdTarget 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Disable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
apc> subfdRstkWh
1. Normal,Open,160A,0kWh,12/27/2012
apc> subfdTarget 1
1. Normal,Open,160A,0kWh,12/27/2012
2. Disable,Disable,95%,Enable,75%,Enable,25%,Enable,5%,Enable
Vue de la page 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 115 116

Commentaires sur ces manuels

Pas de commentaire