47User Guide InfraStruxure 150kVA Power Distribution Unit
brkrThrLo
Access: Administrator, Device
Description. Configure the low load alarm threshold and warning alarm on the breaker selected by the
brkrTarget and brkrPanel commands. Valid threshold values are 0-100% where ThrMx > ThrHi > ThrLo
> ThrMn.
Parameters: [<thresh>] [<enable|disable>]
(Thresh = % rated load )
Example:
apc> brkrstatus 2
1. 1.2,Newname 1.2,Newloc 1.2,Unknown,30A,50A,Normal,30.2kW,60.2kWh,11/08/
2012
2. 1.2,L1,10.2A,34.0%,1.4,L2,10.4A,34.6%,1.6,L3,10.6A,35.3%
3. 1.2,Enable,85%,25A,Enable,65%,19A,Enable,10%,3A,Enable,1%,0A,Enable
apc> brkrthrLo 13 disable
1. 1.2,Enable,85%,25A,Enable,65%,19A,Enable,13%,3A,Disable,1%,0A,Enable
Error Messages: E102
brkrThrMn
Access: Administrator, Device
Description. Configure the minimum load alarm threshold and critical alarm on the breaker selected by
the brkrTarget and brkrPanel commands. Valid threshold values are 0-100% where ThrMx > ThrHi >
ThrLo > ThrMn.
Parameters: [<thresh>] [<enable|disable>]
(Thresh = % rated load)
Example.
apc> brkrstatus 2
1. 1.2,Newname 1.2,Newloc 1.2,Unknown,30A,50A,Normal,30.2kW,60.2kWh,11/08/
2012
2. 1.2,L1,10.2A,34.0%,1.4,L2,10.4A,34.6%,1.6,L3,10.6A,35.3%
3. 1.2,Enable,85%,25A,Enable,65%,19A,Enable,13%,3A,Disable,1%,0A,Enable
apc> brkrthrMn 5 disable
1. 1.2,Enable,85%,25A,Enable,65%,19A,Enable,13%,3A,Disable,5%,1A,Disable
Error Messages: E102