Installation ProceduresConnect DC Power Wiring
990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 31
Cascade XR Battery Enclosures
If you have multiple XR Battery Enclosures as part of your InfraStruXure system, you can cascade XR
Battery Enclosures to form a “daisy-chain” to a Symmetra PX UPS. Starting with the XR Battery
Enclosure furthest away from the UPS:
1. Route DC output cables and the ground cable (coiled on the floor of the enclosure) from one XR
Battery Enclosure to the next XR Battery Enclosure through the adjacent holes in the side panels of
the enclosures.
2. Connect the DC output cables from one XR Battery Enclosure to the DC Input Breaker of the next
XR Battery Enclosure [(+) to (+), (CT) to (CT), (–) to (–)].
3. Connect the ground wire from one XR Battery Enclosure to the grounding stud on the next XR
Battery Enclosure.
XR (–)
XR (+)
XR
(
CT
)
Battery Enclosure
X
R (+) XR (CT) XR (–)
DC INPUT
XR (+) XR (CT) XR (–)
DC OUTPUT
X
R (+) XR (CT) XR (–)
DC INPUT
XR (GND)
Battery Enclosure
To
Battery
Enclosure
To
UPS