990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 79
Appendix B : Single-Line Diagrams
2/0
Load Port
Option
0W1873
V
I
2A
A
S
Lamps
Shunt Trip
Aux Switch
Dual Aux Switch
Current Monitoring
Voltage Monitoring(RMS)
320A
4P
Q2
2A
V
I
0W1874
Q1
360A 3P
2A
0W1865
Bypass
Output
FL=121A
Mains
Input
Symmetra
PX
80kW
2/0
0W1862
I
80A
20A
20A
20A
20A
I
42-Position
400-Amp Rated
Panel
2/0
320A
Q3
H3
All Wiring
4/0 Unless Noted
0W1870
80A
Sub Feeds
0W1871
I
80A
0W1860
4P
2A
I
I
I
I
I
I
I
80A
80A
This drawing and specifications herein are the property of American Power Conversion
and shall not be reproduced or copied or used in whole or par as the basis for the manufacture
or sale of items without written permission from APC.
80kW PDU with System Bypass 208V, 480V, or 600V Input, Single-feed, with Transformer
Bottom Feed
Option
600V
480V
208V
S
V
600V: 0W1782
480V: 0W1782
208V: 0W1783
500
MCM
A
AC
Mains
GND
T
S1
225A/400A
3P
208V
112.5kVA
600V: 0W1815
480V: 0W1814
208V: 0W1810
H3