990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 49
Start-Up Procedure
Safety warnings
This section provides instructions on how to perform a system start-up. Do not skip any steps in this
procedure.
Electrical Hazard:
Only APC Field Service Engineers or qualified, APC-trained
personnel may perform a system start-up.
Warning: Do not install any batteries into the XR Battery Enclosure or power
modules into the Symmetra PX UPS until instructed to do so.
Ensure that all power is off
1. Set the UPS System Enable switch to OFF.
2. Set the XR Battery Enclosure DC Disconnect circuit breaker to OFF.