Start-Up Procedure
52 InfraStruXure System – Service Manual – Installation and Start-Up 990-1467C
7. Install at least one power module in the Symmetra PX UPS.
Install power modules starting from the lowest available shelf. Push each module completely into
the enclosure.
Heavy: Use two people to lift and install power modules.
8. Secure the power module:
a. Tighten the screws on each side of the power module.
b. Turn the locking latch clockwise until the arrow on the knob faces the power module.
Note: The power module will not start unless the locking latch is engaged.