USERS GUIDE
network management card
80
Smart-UPS, Matrix-UPS, or Symmetra UPS. You can use diagnostics
options to perform the following tests.
For the results of the last self-test and last runtime calibration:
In the Web interface, use the Diagnostics page.
In the control console, use the option Detailed Status
(Smart-UPS or Matrix-UPS models) or Detailed
UPS
Information (Symmetra or Silcon UPS models).
Test Definition
Self-Test Perform a self-test of the UPS.
Simulate Power
Failure
Causes the UPS to test its ability to switch to battery operation.
Start/Stop
Runtime
Calibration
Initiates (or cancels) a runtime calibration, a process which
calculates how much runtime the UPS has available.
N
OTE: You can perform a runtime calibration only when the battery is
at 100% capacity.
Test UPS Alarm
(Smart-UPS
or
Matrix-UPS)
Causes a Matrix-UPS to generate an alarm tone, and a Smart-UPS
to generate an alarm tone and flash its front panel lights.
If the Smart-UPS is a member of a Synchronized Control Group:
In the Web interface, this option always tests the alarms of all
enabled members of the group.
In the control console, you are prompted to choose whether to
apply the action to the initiating UPS or to all members of the
group.
In SNMP, you can set the OID upsAdvControlFlashAndBeep to
either option: flashAndBeep (2) to test the alarm of an individual
UPS or flashAndBeepSyncGroup (3) to test the alarms of all
enabled group members.