USERS GUIDE
network management card
81
Symmetra PX UPS. Use buttons on the Diagnostics page in the Web
interface to perform self-tests (Tests...) or runtime calibrations
(Calibrate...).
Scheduled UPS self-tests
To schedule a self-test:
In the Web interface, select Diagnostics on the UPS menu, then use
the Auto Self-Test option.
In the control console, from the UPS menu:
For Symmetra and Symmetra PX UPS models, select Scheduled
Tests.
For Smart-UPS or Matrix-UPS models, select Configuration,
General, and Self-Test Schedule.
The scheduling option allows you to control when a UPS self-test occurs.
The available selections are Never, UPS Startup, Every 7 Days, or Every
14 Days.
For the results of the last self-test and last runtime calibration, and
the status of intelligence modules, power modules, batteries, and
the communication bus and subsystems:
In the Web interface, use the Diagnostics page.
In the control console, use the Detailed UPS Information
option.