Installation ProceduresConnect AC Power and Control Wiring
990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 27
Connect AC power wiring.
1. Attach the bypass wires (L1, L2, L3, N) to the four UPS bypass bus bars with corresponding labels
(
).
2. Attach the input wires (L1, L2, L3, N) to the four UPS input bus bars with corresponding colors
and labels (
). And, attach the input ground wire (G) to the ground lug to the right of the input bus
bars marked .
3. Attach the output wires (L1, L2, L3, N) to the four UPS output bus bars with corresponding colors
and labels (
).
The following illustration shows the UPS buswork and the order in which you need to make the
connections. The numbers in the illustration correspond to the numbered steps above (13).
Electrical Hazard: The conductors are not interchangeable, and must be terminated in
the correct location to prevent damage to the system and connected equipment.