Installation ProceduresConnect DC Power Wiring
32 InfraStruXure System – Service Manual – Installation and Start-Up 990-1467C
Connect power cables from the XR Battery Enclosure to the Symmetra PX UPS
1. Route the XR Battery Enclosure DC output cables to the Symmetra PX UPS through the hole in the
adjacent side panels.
2. Connect the XR Battery Enclosure DC output cables to the Symmetra PX UPS DC input terminal
[(+) to (+), (CT) to (CT), (–) to (–)].
Warning: Text goes here.Tighten the lugs on the terminals only to the torque specified:
the power terminal lug diameter is 10 mm with a torque value of 53 lb/in (6Nm).
3. Connect the XR Battery Enclosure ground cable to the Symmetra PX UPS ground stud.
XR (+)
Battery Enclosure
UPS
R (+) XR (–) XR (CT)
DC INPUT
XR (+) XR (CT) XR (–)
DC OUTPUT
XR (+) XR (CT) XR (–)
DC INPUT
XR (–)
XR (GND)
XR (CT)