APC PD80G6FK1-M Manuel de service Page 36

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 96
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 35
Installation ProceduresConnect AC Power and Control Wiring
28 InfraStruXure System – Service Manual – Installation and Start-Up 990-1467C
Connect control wiring.
4. Connect the EPO control wires from the PDU and Battery Enclosure to the EPO board on the
UPS. The control wires are harnessed and coiled in the floor of the PDU and Battery Enclosure,
respectively. The PDU harness connects to a 4-pin molex connector labeled J6 and the Battery
Enclosure harness connects to a 4-pin molex connector labeled J8.
14 13 12 11 10 9 8 7 6 5 4 3 2 1
4321
8765
21
43
1 Internal Power +24V Supply
2/3 Relay Coil 1
4 Ground
J6—Connect from PDU0W4510C
J6
J8
J8—Connect 0W1696
from Battery Enclosure
1 Internal Power
+24V Supply
2/3 NC
4 Ground
2
1
4
3
psx0328a