Site PlanningBasic Installation Procedure
990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 15
7. Connect utility conductors to the PDU.
A licensed electrician must connect utility power.
For instructions, see Certified Electrician’s Instructions (990-1469A) included with
your InfraStruXure PDU documentation.
8. Connect AC power and control wiring.
See page 26 for detailed instructions.
9. Connect DC power wiring.
See page 30 for detailed instructions.
10. Connect an EPO switch to the PDU user connection plate.
See page 33 for detailed instructions.
11. Connect user input contacts and relay outputs to the PDU user connection plate, if applicable.
See page 37 for detailed instructions.
12. SeeInstall Shielding Troughs, Shielding Partitions, and Cable Ladders.
See page 39 for general information.
For detailed information and grounding instructions, see the instruction sheet
included with the Shielding Troughs and Shielding Partitions
(990-1393B).
For more information on installing and grounding the Cable Ladders see the
instruction sheet included with the cable ladders (990-1576).
13. Install the Rack Automatic Transfer Switches (ATS), Rack Power Distribution Units, and other
InfraStruXure rack-mount devices.
For instructions, see the manuals included with your Rack ATS, Rack PDU, or other
InfraStruXure rack-mount device.
14. Route and attach power cables to RDPs and to each Rack ATS and/or Rack PDUs.
See page 41 for detailed instructions.
15. Route and attach communication cables to the InfraStruXure Manager hub (or switch).
See page 46 for detailed instructions.