Start-Up Procedure
62 InfraStruXure System – Service Manual – Installation and Start-Up 990-1467C
Return from maintenance bypass operation
Note: The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to operate
the Q2 circuit breaker.
1. Close (turn ON) the Q2 circuit breaker on the InfraStruXure PDU.
Note: The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe to operate
the Q3 circuit breaker
1. Command the UPS into static bypass operation through the UPS display interface:
a. Press the
ESC key to open the top-level
menu.
Top-Level Menu
a. Select Control on the top-level menu, and
press the
ENTER key.
b. Select UPS Into Bypass on the Control
menu, and press the
ENTER key.
Control Menu
a. On the next screen: select Ye s , U P S into
Bypass, and press the
ENTER key.
Confirmation Screen
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS into Bypass
No, Abort