USER’S GUIDE
NetBotz Rack Monitor 200
7
Watchdog Features
Overview
To detect internal problems and recover from unanticipated inputs, the Main Module
uses internal, system-wide watchdog mechanisms. When it restarts to recover from an
internal problem, a System: Warmstart event is recorded in the event log.
Network interface watchdog mechanism
The Main Module implements internal watchdog mechanisms to protect itself from
becoming inaccessible over the network. For example, if the Main Module does not
receive any network traffic for 9.5 minutes (either direct traffic, such as SNMP, or
broadcast traffic, such as an Address Resolution Protocol [ARP] request), it assumes
that there is a problem with its network interface and restarts.
Resetting the network timer
To ensure that the Main Module does not restart if the network is quiet for 9.5 minutes,
the Main Module attempts to contact the Default Gateway every 4.5 minutes. If the
gateway is present, it responds to the Main Module, and that response restarts the 9.5-
minute timer. If your application does not require or have a gateway, specify the IP
address of a computer that is running on the network most of the time and is on the
same subnet. The network traffic of that computer will restart the 9.5-minute timer
frequently enough to prevent the Main Module from restarting.