USER’S GUIDE
NetBotz Rack Monitor 200
30
Sensors Connected, but Software Interface
Shows “0 Connected”
This problem can occur if you have one or more older remote sensors, Temperature
Sensors with Digital Display (AP9520T) or Temperature/Humidity Sensors with Digital
Display (AP9520TH), connected to your system. If you have one or more remote
sensors connected to your system, follow the troubleshooting procedure under
Software Interface Shows “Err” on page 29 to determine if you have an older sensor. If
you do not have any remote sensors connected to your system, contact APC
Worldwide Customer Support for further assistance.
Yes Older sensors with older firmware can cause Err to appear.
1. To identify any older sensors:
• Check the serial number. The serial number for older units will
be less than ZA0635011442.
• Remove then reapply power by disconnecting then connecting
the cable to the sensor in port. Note whether the firmware
version number appears during the start-up sequence. Older
units will not display the software version number. If v 1.2.3 or
higher appears, the sensor is running the new firmware and
should work with your system.
2. Remove any old sensors from your system. The problem should
be resolved when all older sensors with a digital display are
removed from your system.
3. Contact APC Worldwide Customer Support for further
assistance. For the older sensors, be sure to have the model
number and serial number available.
Do you have one or more Temperature Sensors with Digital Display (AP9520T) or
Temperature/Humidity Sensors with Digital Display (AP9520TH) connected to your
system?