USER’S GUIDE
NetBotz Rack Monitor 200
37
To configure a sensor’s threshold or rate of change settings: Click the sensor
name. Click Threshold Settings or Rate of Change Settings, alter the settings (see
descriptions below), then click Apply.
Threshold Settings
Minimum Temperature
Threshold
Set the minimum temperature threshold for this sensor. If the
temperature drops below this threshold, an alarm occurs.
Low Temperature
Threshold
Set the low temperature threshold for this sensor. If the temperature
drops below this threshold, an alarm occurs. This threshold must be
greater than Minimum Temperature Threshold.
High Temperature
Threshold
Set the high temperature threshold for this sensor. If the temperature
rises above this threshold, an alarm occurs. This threshold must be
greater than the sum of Low Temperature Threshold and
Temperature Threshold Hysteresis.
Maximum Temperature
Threshold
Set the maximum temperature threshold for this sensor. If the
temperature rises above this threshold, an alarm occurs. This
threshold must be greater than High Temperature Threshold.
Temperature Threshold
Hysteresis
The difference between the temperature threshold violation and the
clearing point. Increasing this value prevents frequent alarms if
temperature wavers slightly above and below the threshold before
corrective actions restore the temperature to the clearing point.
Minimum Humidity
Threshold
Set the minimum humidity threshold for this sensor. If the humidity
drops below this threshold, an alarm occurs.
Low Humidity Threshold Set the low humidity threshold for this sensor. If the humidity drops
below this threshold, an alarm occurs. This threshold must be higher
than Minimum Humidity Threshold.
High Humidity
Threshold
Set the high humidity threshold for this sensor. If the humidity rises
above this threshold, an alarm occurs. This threshold must be higher
than the sum of Low Humidity Threshold and Humidity
Threshold Hysteresis.
Maximum Humidity
Threshold
Set the maximum humidity threshold for this sensor. If the humidity
rises above this threshold, an alarm occurs. This threshold must be
greater than High Humidity Threshold.